Valve Authority Calculator

Enter the control valve’s pressure drop and the rest-of-circuit pressure drop (coil + piping + fittings) to see the resulting valve authority, its control-quality tier, and which valve type fits that result — using the same authority formula and three-tier scale referenced above.

Circuit Inputs

N = ΔP(valve) ÷ [ΔP(valve) + ΔP(circuit)]
Coil + piping + fittings pressure drop, excluding the valve itself

Result

Valve authority (N)
Enter both pressure drops to see the control-quality tier and valve recommendation.
Directional guidance based on the authority formula and general engineering thresholds referenced on this page — exact breakpoints vary slightly by source and application. Confirm final valve selection with your Koven Air applications engineer.