Koven Climate-Match Derating Selector

Air-cooled capacity moves with ambient and leaving-water temperature. Check the correction factor before you lock a selection.

Corrected capacity factor
Effective capacity at your conditions— kW
Change vs nominal (35°C / 7°C)
Confirm on Koven’s test bench →
AmbientLWT 5°CLWT 7°CLWT 12°C
28°C0.961.051.18
35°C0.911.001.12
40°C0.860.941.06
43°C0.820.901.01

Typical directional correction factors (nominal = 35°C ambient / 7°C LWT = 1.00). Sanity-check only — Koven confirms the exact rating per unit. Standard catalogue rates to 43°C; hotter design ambients are confirmed with first-party high-ambient test data.