Lithium Battery Dry-Room Calculators

Four quick estimators for sizing, energy, dew-point targeting, and humidity conversion. These are engineering approximations for early scoping — a Koven Air verification calculation confirms the final specification.

1 · Moisture-Load & Dehumidifier Sizing

From room size, air changes, and dew points, estimate the process airflow and moisture-removal duty your dehumidifier must deliver.

Process airflow (m³/h)
Moisture removal duty (kg/h)

Enter the dew point of the air actually reaching the rotor — mostly recirculated dry-room air in a sealed room (≈ −15 to −20°C), or the outdoor dew point for a 100%-fresh-air design (which multiplies the duty). Δ humidity ratio via Magnus saturation × 1.2 kg/m³ density; infiltration and internal loads add to this — an estimate, not a final duty.

2 · Regeneration Energy & Heat-Pump ROI

Compare annual regeneration electricity for conventional electric heat vs a high-temp heat pump, and estimate simple payback.

Annual electricity saving ($)
Simple payback (years)

Saving = conventional annual × reduction%. Published vendor/peer-reviewed examples put heat-pump regen cuts in a ~60–88% band; the exact figure depends on your baseline, waste-heat recovery, and rate. Illustrative only.

3 · Dew-Point Ladder Selector

Pick your process zone to see the typical dew-point target, indicative air changes, and the right-sizing note — over-drying wastes energy.

ZoneDew pointAir changesNote
General dry-room / return−30 to −45°CdpRH < 1%
Cell assembly (baseline)−40 to −45°Cdp~30–60 ACHMainstream design point
Deep cell assembly−60°Cdp~180 ACHEnergy rises steeply — justify it
Electrolyte filling (critical)down to −80°CdpHigher (micro-env)Micro-environment, not whole room

No single mandatory global dew-point standard exists; the target comes from your process specification. Cleanliness is graded separately to ISO 14644-1.

4 · Relative Humidity ↔ Dew Point

Convert between RH and dew point at a given room temperature (Magnus approximation).

Dew point (°C) at that temperature & RH

At 23°C, ~0.5% RH ≈ −40°C dew point — the mainstream battery dry-room baseline.

Get a Koven Air verification calculation for your dry room →