Four quick estimators for sizing, energy, dew-point targeting, and humidity conversion. These are engineering approximations for early scoping — a Koven Air verification calculation confirms the final specification.
1 · Moisture-Load & Dehumidifier Sizing
From room size, air changes, and dew points, estimate the process airflow and moisture-removal duty your dehumidifier must deliver.
Enter the dew point of the air actually reaching the rotor — mostly recirculated dry-room air in a sealed room (≈ −15 to −20°C), or the outdoor dew point for a 100%-fresh-air design (which multiplies the duty). Δ humidity ratio via Magnus saturation × 1.2 kg/m³ density; infiltration and internal loads add to this — an estimate, not a final duty.
2 · Regeneration Energy & Heat-Pump ROI
Compare annual regeneration electricity for conventional electric heat vs a high-temp heat pump, and estimate simple payback.
Saving = conventional annual × reduction%. Published vendor/peer-reviewed examples put heat-pump regen cuts in a ~60–88% band; the exact figure depends on your baseline, waste-heat recovery, and rate. Illustrative only.
3 · Dew-Point Ladder Selector
Pick your process zone to see the typical dew-point target, indicative air changes, and the right-sizing note — over-drying wastes energy.
| Zone | Dew point | Air changes | Note |
|---|---|---|---|
| General dry-room / return | −30 to −45°Cdp | — | RH < 1% |
| Cell assembly (baseline) | −40 to −45°Cdp | ~30–60 ACH | Mainstream design point |
| Deep cell assembly | −60°Cdp | ~180 ACH | Energy rises steeply — justify it |
| Electrolyte filling (critical) | down to −80°Cdp | Higher (micro-env) | Micro-environment, not whole room |
No single mandatory global dew-point standard exists; the target comes from your process specification. Cleanliness is graded separately to ISO 14644-1.
4 · Relative Humidity ↔ Dew Point
Convert between RH and dew point at a given room temperature (Magnus approximation).
At 23°C, ~0.5% RH ≈ −40°C dew point — the mainstream battery dry-room baseline.