Sensible Cooling Load and Dew-Point Guard Calculator

Estimate the sensible load and test whether the proposed chilled-water temperature stays above the entering-air dew point. This is a preliminary design check, not a replacement for Koven Air’s coil-selection software.

Enter design conditions

Preliminary result

8.0 kW Sensible cooling load
13.4°C Calculated dew point
14.9°C Minimum water temp (with margin)
3.0°C Air dry-bulb drop
Recalculate to check the proposed water temperature.

Method: Qₛ ≈ 1.2 × airflow (m³/s) × entering-to-leaving temperature difference. Dew point uses the Magnus approximation; actual coil surface temperature, fouling, local humidity peaks and control tolerance still require engineering verification.

Send this load to Koven Air Engineering