Get in Touch with Koven Air Company
2-Row vs 3-Row Dry Cooling Coil Comparator
Compare Koven Air’s supplied reference performance at 8,000 m³/h, 2.0 m/s face velocity and 23°C / 55% relative-humidity entering air. Final performance changes with geometry, water temperature and project conditions.
| Reference parameter | 2-row coil | 3-row coil |
|---|---|---|
| Reference airflow | 8,000 m³/h | 8,000 m³/h |
| Reference face velocity | 2.0 m/s | 2.0 m/s |
| Sensible capacity | 7.8 kW | 11.0 kW |
| Water-side pressure drop | 6.7 kPa | 16.9 kPa |
| Capacity per kPa | 1.16 kW/kPa | 0.65 kW/kPa |
Preliminary comparison
Enter a required load to see which reference point clears it.
Engineering boundary: This tool compares one supplied reference condition only. It does not scale capacity linearly to other airflow rates and does not select tube circuits, coil area, row count or valve size.



![Commercial Rooftop Unit Guide: Types, Sizing & Costs [2026]](https://kovenair.com/wp-content/uploads/2026/07/commercial-rooftop-unit-guide-featured-2-150x150.png)
